Reviveaire has dedicated significant time and resources to testing and certifying the Aireshield.
Prior to evaluating it in controlled lab settings, we tested our environmental air filter in real-world conditions. An earlier prototype of the Aireshield was installed in a residential home in Boca Raton, Florida, in three different rooms, connected to the supply grill of an existing HVAC system. Below are some of the test results:
Reviveaire partnered with AMC Engineering and Environmental Services, an independent air quality contractor, to conduct certified testing for mold spores and other pathogens. Using scientific instruments, AMC Engineering and Environmental Services measured the air quality before and after one hour of using the Aireshield prototype. The results, detailed below, show a significant reduction in harmful pathogens and mold spores.
Mold Onsite Test Results
Mold Onsite Test Results
Pathogen removal effectiveness:
Lms technologies ms2 bacteriophage (ASHRAE 241)
Standard 241 corrected MS2 eff: 97.2%, Vacs (CFM) = 57.1, tested by LMS Technologies.
Innovative Bioanalysis SARS-CoV-2
Innovative Bioanalysis, third party tested SARS-CoV-2, resulting in 99.97% after 60 minutes as well as Omicron.
Chinese Center For Disease Control & Prevention Test Report
Staphylococcus Albus Disinfection: 99.99% reduction by Chinese Center for Disease Control & Prevention
SARS SURROGATE INTERTEK REPORT
TEST PARAMETER (W FILTER) | TEST RESULT | NATURAL DECAY RESULT | UNITS | |
ORGANISM | SPECIES | COLIPHAGE ฯX174 | — | |
ATCC N. | 13706-B1 | — | ||
CHALLENGE CONCENTRATION | 5.0 X 109 | PFU/mL | ||
SAMPLES | 0 | TNTC (2628) | TNTC (2628) | PFU |
15 | TNTC (2628) | TNTC (2628) | PFU | |
30 | TNTC (2628) | TNTC (2628) | PFU | |
45 | 234 | TNTC (2628) | PFU | |
60 | 156 | TNTC (2628) | PFU | |
75 | 66 | TNTC (2628) | PFU | |
90 | 21 | TNTC (2628) | PFU | |
105 | 10 | TNTC (2628) | PFU | |
120 | 10 | TNTC (2628) | PFU | |
RESULTS | — | 99.6% |
Phi-X174, a surrogate for SARS-CoV-2, achieved an inactivity rate of 99.7% after 60 minutes in the test chamber.
S. EPIDERMIDIS BACTERIA INTERTEK
TEST PARAMETER (W FILTER) | TEST RESULT | NATURAL DECAY RESULT | UNITS | |
ORGANISM | SPECIES | S. Epidermidis | — | |
ATCC N. | 1228 | — | ||
CHALLENGE CONCENTRATION | 8.8 X 108 | CFU/mL | ||
SAMPLES | 0 | TNTC (2628) | TNTC (2628) | CFU |
15 | TNTC (2628) | TNTC (2628) | CFU | |
30 | TNTC (2628) | TNTC (2628) | CFU | |
45 | 218 | TNTC (2628) | CFU | |
60 | 177 | TNTC (2628) | CFU | |
75 | 111 | TNTC (2628) | CFU | |
90 | 108 | TNTC (2628) | CFU | |
105 | 76 | TNTC (2628) | CFU | |
120 | 59 | TNTC (2628) | CFU | |
RESULTS | — | 97.7% |
BACTERIA TESTED – S. Epidermidis kill rate of 97.7% after only 2 hours in the test chamber.
Guangzhou Institute of Microbiology H1N1 test
H1N1 Disinfection: 99.99% reduction by Guangzhou Institute of Microbiology using a 1 hour chamber test.
Ozone Test Results:
CSA Test: Ozone Emissions at Low Flow Rate
Eight hour time weighted average, 0.935 PPB.
CSA Test: Ozone Emissions at High Flow Rate
Eight hour time weighted average, 0.598 PPB.
ASHRAE Standard 241, 24-Hr Ozone Test
The Aireshield was energized in an ASHRAE 52.2 test duct, connected to a 1007 ft3 test chamber recirculating the airflow at 200 CFM for a 24-hour period.
There was no ozone generation observed during this test period. The average ozone concentration over this 24-hour period was 2.33 ppb.
Particulate reduction using non thermal plasma:
The Aireshield when used in concert with a MERV 8 post filter will achieve similar performance as a MERV13 after 120 minutes in an environmental chamber.